 Description  Miscellaneous
 Notes 
1825 Franco, Jerry 2019-07-24  409 sink is cracked.   182254 (7/25: Henry to check into resin solution.) Emailed Lee and Jason 9/23. 9/30 Henry measured for a new sink to replace the cracked one. 
2123 Fire Marshal 2019-11-182019-11-29  Need to move all of the trash and equipment out from under the basement stair well. Per the Fire Marshal    
2273 Shop, Building 2020-03-112020-03-20  Can we have a work order to replace the senior swing on door 2B on the east side of the building.The door will not open.   SR#198008 
2398 Harrison, Kameron 2020-08-282020-08-31  The action requested is as follows: Chemistry ADA door east side main atrium entrance. Will not open with the button.    BU-194339 
2453 Mechref, Yehia 2020-10-152020-11-06  Check sliding door fridge 2 of 2 in 408, parts/pieces inside    
2583 Franco, Jerry 2021-01-252021-01-29  The sash on the center hood is not working in room 201. Can we get this checked please.   SR#213497 
2594 Franco, Jerry 2021-02-082021-02-26   One of the light fixtures in the cold room looks like its starting to fall off the ceiling. Can we get it checked please.   BU-202560 
2602 Shop, Building 2021-02-092021-02-19  The swinging door between 327 and 326 has hinges coming off the wall. It is causing the door to slam into the door frame. Can we get this checked please.    Request # 214433 
2614 Shop, Building 2021-02-162021-03-12  Chemistry small steam leak in Mech room 1m2.   BU-203022  
2625 Shop, Building 2021-02-232021-02-26  Chemistry Can we have all of the hall floors mopped please   CS-22689  
2609 Shi, Huazhong 2021-02-242021-02-26  The space temp in room 309 is very warm. Can we get this checked asap.   SR# 215511 
2610 Shop, Building 2021-02-242021-02-26   The clock on the west wing in the basement is showing 8:45 and its 2. Can we possibly get a non atomic clock for this area? It doesnt get a signal to correct the time.   BU-203481 
2617 Shop, Building 2021-03-012021-03-12  There are a couple tile that are popping up in the hall in front of 019. They aren�t a tripping hazard at this time but they could become one. Also there is possibly some black astic underneath so we might need the insulation shop.   BU-203718 
2615 Pfeiffer, Charles W. 2021-03-022021-03-02  he compressed air continues to drop in room 017 sending some of the machinery in the machine shop into alarm. The compressor also feels like it is getting really warm. Can we get this checked out please.   BU-203775 
2620 Mechref, Yehia 2021-03-052021-03-12  The exterior door on the center wing on the west side is whistling and you can see daylight around the frame. Can we have this door checked please.   SR # 216197 
2618 Mechref, Yehia 2021-03-052021-03-12  There is a loud noise on the third floor center wing stairwell coming from above. It sounds like bearings may be going out on an exhaust fan on the roof. you can also hear it outside on the ground. /can we get this checked please.   SR#216194 
2619 Mechref, Yehia 2021-03-052021-03-12  We need the 1st floor halls stripped and waxed. There is tape residue from a remodel that needs to be removed please.   SR # 216196 
2622 Shop, Building 2021-03-082021-03-12  CHEMISTR-0R1 One of the soap dispensers is not working. It may be out of batteries but I�m not sure. Can we have it looked at please    CS-22768 
2623 Shop, Building 2021-03-082021-03-12  CHEMISTR-022 We have some compressed air issues in room 022. Can we get this checked please.   BU-204281 
2630 Unruh, Daniel 2021-03-092021-03-19   There are several lights out in room 005. Can we get them changed.   BU-204357 
2627 Shop, Building 2021-03-102021-03-26  The EF that serves the hoods in room 122 is making a lot of noise. Can we get checked please.   BU-204387 
2632 Shop, Building 2021-03-112021-03-19  One of the fume hoods in room 301 is not working. It is the west hood. Can we have this checked    BU-204466 
2634 Shop, Building 2021-03-112021-03-19  Can we get the carpet in room 104 cleaned? In the process of stripping and waxing there is some residue on the carpe    CS-22787 
2635 Pool, Douglas H. 2021-03-112021-03-19  The clock in room 207 is no longer working. Can we get this checked please.    BU-204433 
2631 Shop, Building 2021-03-122021-03-19  The trash can 2r2 has fallen off the wall. Can we get it checked and repaired if possible.   CS-22790  
2665 Kumar, Mallika 2021-03-122021-03-26  The space temp in 304 is very warm can we get this checked please.   BU-204532  
2664 Shop, Building 2021-03-152021-03-31  There is a plugged drain in room 1M2 that is not letting air handler condensation drain. Can we get this checked please.   BU-204529 
2651 Shop, Building 2021-03-182021-04-09   The action requested is as follows: Chemistry RM 324 There is a condensation leak coming from a refrigeration line in the ceiling in room 324. Can we have this checked out please.   BU-204838  
2638 Franco, Jerry 2021-03-222021-03-23  217131, BU-204951: Fume hood in 317 is not working.    
2637 Zou, Qingya 2021-03-22  217095, BU-204922: 407 is not cooling    
2650 Shop, Building 2021-03-222021-04-02  Chemistry 325 One of the fume hoods is not working in 325. Can we get this checked please.   BU-202481  
2639 Franco, Jerry 2021-03-232021-03-26  217264, BU-205033 : Chemistry-across from the loading dock- top of light pole is hanging off.    
2644 Shop, Building 2021-03-242021-03-24  Open 3rd floor autoclave room for repair    
2653 Harrison, Kameron 2021-03-252021-04-09  The action requested is as follows: Can we get the halls swept and mopped please. Especially the 2nd and 3rd floor. After the dust storms they are a little dusty.   SR# 217460 
2654 Mechref, Yehia 2021-03-252021-04-09  Wen need the office furniture and tables dusted and cleaned in room 328D please. It is covered in a black dust.   SR#217580 
2655 Harrison, Kameron 2021-03-292021-04-02  One of the sinks in room 229 does not have much water flow. Can we get it checked plea   BU-205289  
2658 Shop, Building 2021-03-302021-04-09  There is a sewer smell in the hall west of room 049. Can we get this checked please.   BU-205358 
2660 Shop, Building 2021-03-302021-03-30  One of the hoods in room 323 isn't working can we get it checked please.   BU-205348 
2668 Shop, Building 2021-03-312021-04-04  Can we get offices 328C and 328D vacuumed and dusted please.   SR# 217801  
2672 Gorden, John 2021-04-062021-04-16  Fume hood in room 003 is not working.   BU-205984  
2673 Shop, Building 2021-04-072021-04-30  One of the windows in room 019 is broken can we get this repaired please.   SR#218193 
2671 Franco, Jerry 2021-04-072021-04-09  One of the fume hoods in room 227 is not working. Can we get it checked please.   SR#218190 
2681 Shop, Building 2021-04-122021-04-16  The thermostat in room 001 is hissing. Can we get it checked please.   BU-206222 SR # 218521 
2678 Shop, Building 2021-04-142021-04-23   One of the hoods in room 201 is not working. Can we get it checked please.   BU-206371 SR#218691 
2692 Shop, Building 2021-04-162021-06-04  The lock on the door for room 319 is gummed up and gets stuck in the door so the door does not lock. Also, the door has to be pulled hard to lock. Can we get this checked please.   BU-206458 
2686 Shop, Building 2021-04-272021-04-30  AHU7C is vibrating alot. A new drive was installed yesterday so it may be tied to that. It is currently running at 60htz and before the drive was installed it was running at a slower speed. Can we please get this checked out.   SR # 219428 
2689 Vaughn, Quentin 2021-04-272021-04-30   1st floor hallway There is a light in the hall that is flashing. We need it changed asap. primarycontact:    
2688 Shop, Building 2021-04-282021-05-07   Rm 339 We need lab 339 put back on the master key please.   BU-206790 
2687 Pfeiffer, Charles W. 2021-05-032021-05-03  Chemistry RM 18 The shop is getting cold since the steam has been shut off. Can we have someone come and check it please?   BU-207346 
2700 Vaughn, Quentin 2021-05-072021-05-21  One of the lights in room 407A is out. Can we get this changed please.   SR#220048 
2702 Franco, Jerry 2021-05-122021-05-28   The action requested is as follows: Chemistry floor tiles need replaced in 235.   BU-207782 
2703 Franco, Jerry 2021-05-122021-05-28  The action requested is as follows: Chemistry 227 & 229 fume hoods not working.   BU-207781 
2701 Wilde, Vince 2021-05-202021-05-28  The 20AMP outlet in room 111 is not working. Can we get it checked please.   SR # 220822 
2725 Shop, Building 2021-05-212021-06-04  The action requested is as follows: Chemistry 227 & 229 fume hoods not working   BU-207781 
2723 Shop, Building 2021-05-252021-05-26  Elevator 1 the north elevator is making an odd noise when it reaches the 3rd floor. Can we get this checked please   SR#221058  
2724 Shop, Building 2021-05-252021-06-04  Door 6A on the north side of the building is missing several screws and is about to loose its door closer.   BU-208327  
2713 Forsyth, Donna M. 2021-06-032021-06-11  I have received several complaints that keys are not working on on exterior doors. We need the lock on the North door on the East side of the building checked please.    BU-209172  
2727 Purkiss, LaQuetta 2021-06-082021-06-18  The action requested is as follows: The handle on one of the DI water faucets continually falls off. The faucet needs to be repaired or replaced.   SR# 222449  
2711 Dent, Dorothy 2021-06-082021-07-02  The action requested is as follows: We need the Office 204 added to the painting waiting list please. The occupant would like to look at the approved color choices.   BU-209497  
2726 Forsyth, Donna M. 2021-06-092021-06-25  There is no air blowing in womens rr 1R2. Can we get it checked please.   SR#222242 
2721 Shop, Building 2021-06-092021-06-11  Can we get the ramp and dock cleaned or blown off on the west side of the building. They are full of trash and old leaves.   SR# 222225 
2760 Shop, Building 2021-06-142021-07-30   I have had several complaints about hot and humid spots throughout the 1st floor.   BU-209870 
2757 Franco, Jerry 2021-06-152021-07-09  The center fume hood in lab 115 is not working. Can we get it checked please. Served by EF96   SR# 222742 
2747 Shop, Building 2021-06-222021-07-30  Chemistry It sounds like there is a steam or water leak under a man hole cover on the east side of the building by the ramp on the south wing. Can we get this checked pleas   BU-210261 
2739 Vaughn, Quentin 2021-06-242021-06-30  The action requested is as follows: CHemistry 117B The lights in room 117B have quit working. We need this checked asap.   BU-210249 
2732 Shop, Building 2021-06-302021-07-09  The action requested is as follows: CHEMISTRY The main fire panel on the 1st floor is beeping. I have discussed it with Keith and he said N2L1M93 is not communicating. We need a WO so Keith can come and check it for us please.   BU-210671 
2729 Shop, Building 2021-07-012021-07-09  The action requested is as follows: Elevator one is moving very slowly when it opens and closes. Can we get it checked please.   SR#223845 (7/9 Tech checked the door and it was working fine but that he would keep wtching it.) 
2730 Shi, Huazhong 2021-07-012021-07-09   The action requested is as follows: CHEMISTRY 309 The A/C unit that serves room 309 is not functioning. Can we get this checked please. Ervin is aware of the issue.    BU-210730 
2743 Franco, Jerry 2021-07-012021-07-16  The action requested is as follows: The door for room 235 is hard to get into. The lock is not working properly. Can we get it checked asap   BU-210778  
2755 Rodriguez, Linda 2021-07-022021-07-09  There are parts of paint and plaster fallin off the ceiling in room 09. Can we get this checked please.   BU-210819  
2752 Shop, Building 2021-07-052021-07-09  I have had complaints that this room is warm even before the chill water issues of today. It may be due to a fire damper that closed several weeks ago when the fire suppression system discharged. Can we get it checked please?   SR#224125 
2754 Shop, Building 2021-07-052021-07-09  Chemistry 3M3 is leaking down to the basement.    BU-211188 
2753 Shop, Building 2021-07-052021-07-09  Chemistry Room 101 clock is not working. Can we get it checked please.   BU-211213  
2770 Quitevis, Edward L. 2021-07-122021-07-23  The west side of room 128 has is very moist. At some point there was a leak coming from the room above but it is not wet right now. Can we please get the plumbing checked in room 226 that drops to room 128.   SR# 224595 
2765 Franco, Jerry 2021-07-122021-07-30  Can we have the natural gas turned off to lab 233. The people in the lab never use it and no longer want it to be available.   SR#224535 
2769 Poirier, L. William 2021-07-122021-07-23  Can we have the electronic lock on room 010 replaced with a conventional one keyed to fit same lock as on the inside door.   SR# 224569 
2763 Casadonte, Dominick J., Jr. 2021-07-122021-07-30  We need a quote to have a large section of floor tiles replaced in-front of the hoods in lab 233.   SR# 224527 
2761 Rodriguez, Linda 2021-07-122021-07-16  There is water dripping from the ceiling in room 09 it may be tied to the plaster falling from the ceiling(BU-210407). I checked the labs above and could not find any water under the cabinets or anything.   SR#224522 
2762 Liang, Ruibin 2021-07-122021-07-16  Can we have the floors vacuumed and cleaned in room 012 and 013 please. They have complained about dead roaches on the floor in the area.   SR#224524 
2771 Shop, Building 2021-07-122021-07-23  The humidity is extremely high throughout the building. Doors are swelling and dragging on the frames, especially in 328C and 328D, and paper seems wet. Can we get all of the air handling systems checked please.   SR# 224597 
2788 Shop, Building 2021-07-142021-08-11  CHEMISTRY RM 233 Can we have the natural gas turned off to lab 233. The people in the lab never use it and no longer want it to be available    BU-211545  
2787 Shop, Building 2021-07-152021-08-13  The south hall way on the west side of the building there is a light that is flashing. Can we get this checked please   BU-211762 
2783 Rodriguez, Linda 2021-08-022021-08-27  There is water dripping from the ceiling in room 09 it may be tied to the plaster falling from the ceiling(BU-210407). I checked the labs above and could not find any water under the cabinets or anything.    BU-211540 
2784 Johnson, InEyes 2021-08-022021-08-27  The action requested is as follows: CHEMISTRY 205 It is still cold in office 205. Can we get his checked please.   BU-212514  
2782 Pfeiffer, Charles W. 2021-08-032021-08-06  The action requested is as follows: Room 017-018 are cold. Can we get them checked out please.   Service Request # 226038  
2780 Shop, Building 2021-08-042021-08-27  The action requested is as follows: CHEMISTRY 0M2 One of the water pumps in mechanical room 0M2 is vibrating horribly. I believe it is a domestic water pump. Can we get it checked out please.   BU-212888  
2781 Shop, Building 2021-08-042021-08-20  The nozzle has been fixed and now the wall needs to be cleaned please. Per Scottie Edwards clean walls at this location by FM-200 nozzle.   CS-23825 
2779 Harrison, Kameron 2021-08-062021-08-20  The action requested is as follows: CHEMISTRY 230 The master key is not working to open room 230. Can we get it    BU-213009 
2772 Rodriguez, Linda 2021-08-112021-09-17  Paint shop to paint 125 A, C, D. primarycontact: Kameron Harrison Rich Cartwright approved this to be issued on 16A063 SLVC.   BU-213299  
2777 Franco, Jerry 2021-08-112021-08-27  The DI faucet in room 121 has a small continuous leak that is running across the counter and down the cabinet. We need this checked please.   BU-213287 
2778 Mechref, Yehia 2021-08-112021-08-31  There is currently a machine wired directly with 240v 60A that will be removed where we need the plug. Input // 208V Wire // 8 AWG Breaker // 45A Plug // 6-50P    BU-213283 
2812 Shop, Building 2021-09-012021-10-07  Several of the lights are out in room 222. Can we get them changed please.     BU-210277  
2790 Franco, Jerry 2021-09-032021-09-17  Fume hood is down.   SR#228812 
2792 Shop, Building 2021-09-082021-09-30  The action requested is as follows: We are missing a ceiling tile in the hall in front of room 204. Can we get it replaced please.   SR#229019  
2793 Franco, Jerry 2021-09-082021-09-24  The east hood in lab 209 is not working. Can we get it repaired ASAP please.   SR#229103 
2821 Shop, Building 2021-09-212021-10-08   The thermostat in room 233 is broken. Can we get it fixed please.   BU-215947 
2818 Unruh, Daniel 2021-09-232021-10-22  Several of the lights are out in room 005. Can we get them changed please.   SR# 230354  
2816 Shop, Building 2021-09-242021-10-07  We need a WO to check the air compressor. One of the pressure switches is hanging and could go out soon. Ervin is aware of the issue   SR# 230457 BU-216119 
2813 Shop, Building 2021-09-272021-10-22   The clock In the hall outside of room 049 is not working. Can we get it fixed please?   BU-216225 SR # 230585  
2807 Shop, Building 2021-09-302021-10-15  One of the fume hoods in room 032 is not working. Can we get it checked please.   SR # 230926 BU-21642 
2808 Shop, Building 2021-09-302021-10-15  The action requested is as follows: CHEMISTRY One of the Exhaust fans on the roof is making alot of noise. I can hear it on the ground. Can we get this checked.   SR # 230912 BU-216408 
2806 Hope-Weeks, Louisa J. 2021-10-012021-10-29  The lights constantly go off in the office because of the motion censor. Can we get this checked and moved or removed so it does not go off even when the office is occupied.   BU-216466 SR# 230985  
2804 Pool, Douglas H. 2021-10-042021-11-05  CHEMISTRY 206 The shower in room 206 has a slow steady drip. Can we get it checked please.   BU-216828  
2795 Bennett, Andrew 2021-10-062021-10-29   We need power reinstalled to the plugs in room 323. It was removed during the remodel of room 220 below 323. We need it reinstalled to the outlets on the west wall or new lines run to provide power on the west wall    SR# 231415 BU-217019 
2826 shops 2022-05-112022-05-13  There is water on the floor in room 019. Last year they cleaned out roof drains hoping to fix the issue but it has returned.Can we get it checked asap.   Request # 245501  
2827 Franco, Jerry 2022-05-112022-05-27   The first sink on the north side of the restroom is leaking onto the floor. Can we get it checked please.   Request # 245517  
2824 shops 2022-05-112022-05-20  Room 007 is cold. Can we please get it checked.   Service Request # 245497 
2825 shops 2022-05-112022-05-12  CHEMISTRY 323 There are a couple what looks like roof leaks in 323. Can we get them checked asap.    BU-228840  